ProFire PF3100 Product Manual page 139

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

49. Select "Configure Curves" to set up the FARC profile tables.
50. Configure the table in accordance with safety design documentation and manufacturer specifications as
well as the slope and feedback requirements outlined in the table below for each channel at each firing rate
increment. Refer to the
Scenario
Channel
Cross limiting setting
Air
N/A – Always enabled
Fuel
Enabled
Aux
Disabled
* All unconfigured columns on the table are linearly interpolated from the configured points.
51. Ensure that both Curve A and Curve B are configured correctly and select "Finished".
52. Press
then
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
PF3100 FARC User Guide
Slope Requirement
Cannot decrease
Cannot change direction
No requirements
to advance to the O
Trim Tab.
2
for detailed configuration instructions.
Position feedback requirement
N/A – Always enabled
Must be enabled
Not required
PF3100 Product Manual
DOC-001149 v8.0
139

Advertisement

Table of Contents
loading

Table of Contents