ProFire PF3100 Product Manual page 185

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

Code
Alert Name
UI/Modbus
1073
74
Reserved
1074
75
No Appliance Level/Flow
1075
76
Reserved
1076
77
Appliance Startup Cancelled
1077
78
Appliance Startup Timeout
1078
79
Appliance Startup Mismatch
1079
80
Reserved
1080
81
Controller Disabled
Minimum Controllers Rule
1081
82
Violated
1082
83
Controller Network Wiring Error
1083
84
IO Network Wiring Error
Failed to Prove Airflow While
1084
85
Running
Failed to Prove Airflow While
1085
86
Purging
Multiple Primary Process
1086
87
Temperatures
Primary Process Temperature
1087
88
Configuration Error
Auxiliary Temperature
1088
89
Configuration Error
No Primary Process
1089
90
Temperature Configured
1090
91
UV Flame Detect Fault
1091
92
UV Flame Detect Mismatch
1092
93
UV Input Out of Range
1093
94
UV Input Address Fault
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
The appliance does not have a Local Level/Flow Input enabled.
The appliance startup was cancelled by the User Interface or Modbus card.
The appliance was not able to successfully start all the BMS controllers
within the appliance.
During appliance startup one of the BMS cards reported settings that did
not match the other BMS cards.
This BMS has been disabled in the appliance settings.
Number of BMS Controllers running is less than the Min Controllers
Running setting (BMS Settings > Setup > Commissioning).
An I/O card is connected to the PFRN Controller Network (BMS Controller
terminal 28).
A UI card or Modbus card is connected to the PFRN I/O Network (BMS
Controller terminals 29,30,31 or 32).
The BMS Controller Aux input (configured as a Proof of Airflow input) is de-
energized while in a fuel state, OR
An I/O Expansion input (configured as a Proof of Airflow input) is not
satisfied while in a fuel state.
The BMS Controller Aux input (configured as a Proof of Airflow input) is de-
energized while purging, OR
An I/O Expansion input (configured as a Proof of Airflow input) is not
satisfied while purging.
More than one temperature input is configured as a Primary Process input.
Process Deadband setting is set above 100°C (180°F).
Aux Temp High Temp SP setting is set above 1350°C (2462°F), OR
Aux Temp High Temp SP setting is less than Process Setpoint + 1, OR
Auxiliary Temperature Deadband setting is set above 100°C (180°F)
No temperature input has been configured as a Primary Process input.
UV Pilot card Fault input de-energized.
UV Pilot card Flame On and Flame Off inputs are either (1) both energized,
or (2) both de-energized.
UV Scanner input invalid.
Contact
Internal UV Pilot card fault.
PF3100 Product Manual
Description
Profire.
Contact
Profire.
DOC-001149 v8.0
185