16.10.2.6
LEVEL/FLOW INPUT
Setting
Level/Flow Input Mode
Local Level/Flow Input
Low Level/Flow Restart
4-20 Level/Flow Max
4-20 Level/Flow Min
4-20 High Level/Flow SP
4-20 Low Level/Flow SP
Level/Flow Deadband
Low Level/Flow Delay
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Default
Options
Disabled
Disabled
Dry Contact
4-20
Enabled
Disabled
Disabled
Enabled
Disabled
Disabled
120 L
0 L – Any
31.7 gal
0 L
0 L – Any
0 gal
117 L
0 % - 100 % of Max
31 gal
60 L
0 % - 100 % of Max
15.9 gal
1.5 L
0 % - 6.25 % of Max
0.4 gal
2 s
2 s – 20 s
PF3100 Product Manual
Description
The Level/Flow input is ignored.
The Level/Flow input is connected to a
Level or Flow switch.
The Level/Flow input is connected to
4-20mA Level or Flow transmitter.
The Level/Flow input device is
physically wired to the controller.
The Level/Flow input device is
physically wired to a different
controller in the appliance.
The system transitions into the Waiting
state upon a low-level/flow event and
does not proceed until cleared.
The appliance shuts down on low-
level/flow events.
The maximum reading of the level or
flow transmitter.
The minimum reading of the level or
flow transmitter.
Specifies the transmitter reading above
which the appliance shuts down on
high level/flow.
Specifies the transmitter reading below
which the system registers a low
level/flow event.
Specifies the deadband applied to
prevent fluctuation between states.
Specifies the time for which a low-
level/flow event must be present
before the system acts.
DOC-001149 v8.0
153