16.10.4.2
SYSTEM VOLTAGE
Setting
Default
Controller Voltage
24 V
Voltage Deadband
0.2 V
Low Voltage Restart
Disabled
High Voltage Restart
Disabled
16.10.4.3
OTHER
Setting
Default
Comm Loss Restart
Disabled
BMS User Interface
Enabled
BMS Wait Timeout
2 min
IO Wait Timeout
2 min
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Options
Description
12 V
The controller is supplied by a 12 V power source.
24 V
The controller is supplied by a 24 V power source.
Specifies the deadband applied to the input voltage to prevent
0 V - 0.5 V
fluctuation between states when the reading is near the trip points.
The system automatically restarts following a power loss while
Enabled
running.
The system does not automatically restart following a power loss
Disabled
event.
The system transitions to the Waiting state upon a high voltage
Enabled
event.
Disabled
The system shuts down upon a high voltage event.
Options
Description
The system goes to the Waiting state upon Pilot card
Enabled
communication loss.
Disabled
The system goes to Lockout upon Pilot card communication loss.
Enabled
BMS Enclosure LED indicators enabled.
Disabled
BMS Enclosure LED indicators disabled.
0 min
BMS Wait Timeout setting is ignored.
Specifies the time after which a BMS wait becomes an alarm.
Applicable waits: BMS Low Voltage • BMS High Voltage • BMS Low Fuel Pressure (4-
1 – 120 min
20mA and Dry contact mode) • BMS Low Level/Flow • BMS Level/Flow Open • Loss of
Communications
0 min
IO Wait Timeout setting is ignored.
Specifies the time after which an I/O Expansion wait becomes an
alarm.
1 – 120 min
Applicable waits: I/O Expansion Input Invalid • I/O Expansion Input Low Trip • I/O
Expansion Input High Trip • I/O Expansion Input Open
PF3100 Product Manual
DOC-001149 v8.0
157