13.3 READY STATE

The controller transitions to the Ready state when all alarm conditions are cleared and holds all safety outputs
de-energized. A user can only start the controller from the Ready state.
13.3.1 SAFETY OUTPUT BEHAVIOR - READY STATE
Card
PF3101-00 BMS Controller card
PF3102-00 Ion Pilot card
PF3102-01 UV Pilot card
13.3.2 TRANSITIONS TO THE READY STATE
From
Scenario
Controller was not running at last
power down
Power On
Any
Lockout message acknowledged by
Lockout
user
Alarm
Any
13.3.3 TRANSITIONS FROM THE READY STATE
To
Scenario
Alarm
Any
Waiting
Controller started by user
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Power On
Lockout
Alarm
Ready
Output
Pilot
SSV1
SSV2
Valve
Coil
Ignition Enable
Condition
Low Voltage Restart setting is set to Enabled, AND
No alarm conditions present
Low Voltage Restart setting is set to Disabled, AND
No alarm conditions or unacknowledged lockout messages present
Any
No alarm conditions present
Condition
Alarm condition present
Any
PF3100 Product Manual
DOC-001149 v8.0
Alarm
Waiting
Output State
De-energized
De-energized
De-energized
De-energized
De-energized
Open