5.10 PROOF OF CLOSURE INPUT

5.10.1 DETAILS
Terminals
Name
Type
5.10.2 INTENDED FIELD DEVICE CONNECTIONS
Field Device
Main valve (SSV) proof of closure
switch
Incinerator assist gas valve
(SSV1) proof of closure switch
Incinerator waste gas valve
(SSV2) proof of closure switch
Not Used
5.10.3 SYSTEM BEHAVIOR – PROOF OF CLOSURE INPUT
System Configuration
Proof Of Closure: Disabled
Proof Of Closure: Enabled
Proof Of Closure: Enabled
Incinerator Enable: Disabled
Proof Of Closure: Enabled
Incinerator Enable: Enabled
Incinerator PoC Valve: Waste
Proof Of Closure: Enabled
Incinerator Enable: Enabled
Incinerator PoC Valve: Assist
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
18 & 19
POC
Digital Input
Configuration Requirements
Controller Settings > Inputs > Proof Of Closure
Proof Of Closure: Enabled
Controller Settings > Process Control >
Incinerator Control
Incinerator Enable: Enabled
Incinerator PoC Valve: Assist
Controller Settings > Inputs > Proof Of Closure
Proof Of Closure: Enabled
Controller Settings > Process Control >
Incinerator Control
Incinerator Enable: Enabled
Incinerator PoC Valve: Waste
Controller Settings > Inputs > Proof Of Closure
Proof Of Closure: Enabled
Controller Settings > Inputs > Proof Of Closure
Proof Of Closure: Disabled
Scenario
Controller
POC Input
State
Any
Any
Energized
Any non-main
state
De-energized
Any main fuel
Energized
state
De-energized
Energized
Low Fire
De-energized
Energized
Incinerate
De-energized
Energized
Incinerator
No Assist
De-energized
Energized
Low Fire
De-energized
Energized
Incinerate
De-energized
Energized
Incinerate No
Assist
De-energized
PFRN Controller Network
35 – License Key
27
26
25
4-20mA / Dry
Contact Inputs
Connection Diagrams
Digital Input – Dry Contact
Digital Input – Wet Contact
Digital Input – Dry Contact
Digital Input – Wet Contact
Digital Input – Dry Contact
Digital Input – Wet Contact
N/A
State Transition
Controller Alerts
No effect
N/A
No effect
N/A
Lockout/Alarm
POC Contact Open alarm
No effect
POC Contact Failed to Open warning
No effect
N/A
No effect
N/A
Lockout
POC Contact Open alarm
No effect
POC Contact Failed to Open warning
No effect
N/A
No effect
POC Contact Failed to Open warning
No effect
N/A
No effect
POC Contact Failed to Open warning
No effect
N/A
No effect
POC Contact Failed to Open warning
No effect
N/A
No effect
N/A
Lockout
POC Contact Open alarm
PF3100 Product Manual
DOC-001149 v8.0
PFRN IO Network
33 – Ignition
10A
Switch
PF3101-00
Fuse
BMS Controller
R un Ign it e O n
V1.3
PF3101-00
XX: 00:00: 00:XX: XX
## ## ##
Push Tabs
YYYY-MM-DD
To Remove Key
V# .#. #
24
23
22
21
20
19
18
17
16
15
14
13 12
11 10
9
8
7
6
5
4
3
2
1
STATUS
SPST
NO
80mA
4-20mA
12/24V
Power Input
120 VAC/
120 VDC
MAX
Dry Contact Inputs
Powered Outputs
Relay Output