14.1.1.1
EPX ENCLOSURE MOUNTING
To maintain the hazardous location rating for the EPX enclosure, all the following conditions must be met:
The enclosure lid must be tightened down until it is flush with the base and the locking screw must be fully
•
secured,
Each unused conduit entry port must be sealed with appropriately rated pipe plugs,
•
Any conduit entry ports in use must be sealed in accordance with local electrical code(s),
•
•
All fittings must have at least 5 full threads of engagement,
All fittings must be ¾" NPT.
•
14.1.1.2
TLX ENCLOSURE MOUNTING
To maintain the hazardous location rating for the TLX enclosure, all the following conditions must be met:
The enclosure lid must be fully tightened down,
•
Any conduit entry ports in use must be sealed in accordance with local electrical code(s),
•
•
Each unused conduit entry port must be sealed with appropriately sized and rated pipe plugs,
Thermocouple probe must be installed in an appropriately rated thermowell.
•