14.1.1.1
EPX ENCLOSURE MOUNTING
To maintain the hazardous location rating for the EPX enclosure, all the following conditions must be met:
The enclosure lid must be tightened down until it is flush with the base and the locking screw must be fully
secured,
Each unused conduit entry port must be sealed with appropriately rated pipe plugs,
Any conduit entry ports in use must be sealed in accordance with local electrical code(s),
All fittings must have at least 5 full threads of engagement,
All fittings must be ¾" NPT.
14.1.1.2
TLX ENCLOSURE MOUNTING
To maintain the hazardous location rating for the TLX enclosure, all the following conditions must be met:
The enclosure lid must be fully tightened down,
Any conduit entry ports in use must be sealed in accordance with local electrical code(s),
Each unused conduit entry port must be sealed with appropriately sized and rated pipe plugs,
Thermocouple probe must be installed in an appropriately rated thermowell.