13.1 POWER ON STATE

The controller always enters the Power On state upon power up. All safety outputs are held de-energized, and a
purge event is triggered upon entry into the state. The controller quickly transitions out of the Power On state in
accordance with the state transition tables below.
13.1.1 SAFETY OUTPUT BEHAVIOR - POWER ON STATE
Card
PF3101-00 BMS Controller card
PF3102-00 Ion Pilot card
PF3102-01 UV Pilot card
13.1.2 TRANSITIONS TO THE POWER ON STATE
From
Scenario
Power Off
Any
13.1.3 TRANSITIONS FROM THE POWER ON STATE
To
Scenario
Lockout
Any
Alarm
Any
* via Ready
Controller was not running at last
power down
Ready
Any
Controller was running at last power
Waiting
down
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Power On
Output
Ignition Enable
Condition
Any
Condition
Unacknowledged lockout message present
Alarm condition present
Low Voltage Restart setting is set to Enabled, AND
No alarm conditions present
Low Voltage Restart setting is set to Disabled, AND
No alarm conditions or unacknowledged lockout messages present
Low Voltage Restart setting is set to Enabled, AND
No alarm conditions or unacknowledged lockout messages present
Lockout
Ready
Waiting
Pilot
SSV1
SSV2
Valve
Coil
PF3100 Product Manual
DOC-001149 v8.0
Output State
De-energized
De-energized
De-energized
De-energized
De-energized
Open