16.10.1.7
LOW HEAT STANDBY
Setting
Low Heat Standby Mode
Low Heat Standby Delay
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Default
Options
Disabled
Wait
Disabled
Main Permissive
1 min
1 min – 1440 min
PF3100 Product Manual
Description
The controller does not use Low Heat
Standby functionality
Specifies that the controller transitions
to the Waiting state if all the following
conditions are met for the duration of
the Low Heat Standby Delay setting:
1.
The controller is in the PID
Control state.
2.
The process temperature is
between the Process setpoint
and Low Fire Setpoint.
3.
Basic PID: The firing rate is at
the configured Minimum
Firing Rate.
Cascaded PID: The Primary
setpoint is at the configured
Primary Setpoint Min setting.
Specifies that the controller transitions
to the Pilot state if all the following
condition are met for the duration of
the Low Heat Standby Delay setting:
1.
The controller is in the PID
Control state.
2.
The process temperature is
between the Process setpoint
and Low Fire Setpoint.
3.
Basic PID: The firing rate is at
the configured Minimum
Firing Rate.
Cascaded PID: The Primary
setpoint is at the configured
Primary Setpoint Min setting.
Specifies the time for which the Low
Heat Standby conditions must be met
for the system to initiate a Low Heat
Standby state transition.