9.2.4
SYSTEM BEHAVIOR – REDUNDANT TEMPERATURE INPUTS
A temperature input is redundant if it is measured by multiple thermocouple devices (i.e., one created
temperature input (Temperature Wizard > Create Inputs Tab) is assigned to more than one temperature card
input slot (Temperature Wizard > Temp Modules Tab) either on the same card or on another card).
Scenario
Input Reading
Open or Out of Range
(note 1)
Above High Temp Setpoint
(note 1)
Below High Temp Setpoint
(note 1)
Below Low Temp Setpoint
(note 1)
1
The input reading for redundant inputs is determined by the first communicating input that has a valid temperature reading
(i.e., not open or out of range) only.
High Auxiliary Temperature Warning displayed If temperature is above its configured High Temp Warning Setpoint.
2
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Mode
Disabled or
Display Only
Process Control
Aux Process or
High Temp ESD
Disabled or
Display Only
Process Control
Aux Process or
High Temp ESD
Disabled or
Display Only
High Temp ESD
Process Control or
Aux Process
Process Control
State Transition
Controller Alerts
No effect
Thermocouple Failure Warning
Lockout/Alarm
No Valid Primary Process Temperature
Lockout/Alarm
No Valid Auxiliary Temperature alarm
No effect
N/A
Lockout/Alarm
Primary Process Temperature High ESD
Lockout/Alarm
Auxiliary Temperature High ESD alarm
No effect
N/A
No effect
N/A
Normal Operation – Refer to
No effect
Low Process Temp warning
PF3100 Product Manual
2
Operating Sequence
section for details
DOC-001149 v8.0
60