16.8 OUTPUT CALIBRATION WIZARD

The Output Calibration Wizard is used to calibrate the BMS card and I/O Expansion card 4-20 mA outputs.
36. Disconnect field device from output to be calibrated and connect a process calibrator in its place.
16.8.1 OUTPUTS TAB
37. Select the appropriate output from the list and press
38. Adjust the 4mA value to match the reading on the process calibrator using
39. Adjust the 20mA value to match the reading on the process calibrator using
40. Check the calibration. Use
41. Reconnect field device.
42. Repeat above steps for all outputs listed.
43. Press
then
16.8.2 REVIEW TAB
44. Ensure that there are no errors and select "Accept" to save all changes and exit the Output Calibration
Wizard.
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
6
-
HFV-
7
-
HFV+
8
-
SSV2-
9
-
SSV2+
10
-
SSV1-
11
-
SSV1+
12
-
Pilot-
13
-
Pilot+
14
-
Aux Out-
15
-
Aux Out+
PF3101-00 BMS Controller Card
6
-
HFV-
7
-
HFV+
SSV2-
8
-
9
-
SSV2+
10
-
SSV1-
SSV1+
11
-
12
-
Pilot-
13
-
Pilot+
14
-
Aux Out-
15
-
Aux Out+
PF3101-00 BMS Controller Card
6
-
HFV-
7
-
HFV+
SSV2-
8
-
9
-
SSV2+
10
-
SSV1-
11
-
SSV1+
12
-
Pilot-
Pilot+
13
-
14
-
Aux Out-
15
-
Aux Out+
and
to change the output value and verify against the process calibrator reading.
to advance to the Review Tab.
PF3101-00 BMS Controller Card
m A
D C
0 0 . 0 0 0
.
m A
D C
0 4 . 0 2 0
m A
D C
1 9 . 9 9 0
PF3101-00 BMS Controller Card
1 2 . 0 0 0
6
-
HFV-
7
-
HFV+
8
-
SSV2-
9
-
SSV2+
SSV1-
10
-
11
-
SSV1+
12
-
Pilot-
Pilot+
13
-
14
-
Aux Out-
15
-
Aux Out+
PF3100 Product Manual
DOC-001149 v8.0
and
.
and
.
m A
D C
136