ProFire PF3100 Product Manual page 186

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

Code
Alert Name
UI/Modbus
1094
95
IO Expansion Input Invalid
I/O Expansion POAF Input
1095
96
Invalid
1096
97
IO Expansion Analog Input High
1097
98
IO Expansion Analog Input Low
IO Expansion Digital Input
1098
99
Open
IO Expansion Configuration
1099
100
Error
Invalid Appliance Firing Rate
1100
101
Input
1101
102
Failed to Prove Purge Position
1102
103
Failed to Prove Pilot Position
Failed to Prove Light Off
1103
104
Position
1104
105
FARC Cross Limit Error
FARC Fuel Channel Position
1105
106
Error
1106
107
FARC Air Channel Position Error
1107
108
Reserved
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
An I/O Expansion card input configured as an alarm is not reading a valid
input signal.
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
The I/O Expansion card input configured as a Proof of Airflow input is not
reading a valid input signal.
A 4-20mA I/O Expansion card input configured as an alarm is above its
High Setpoint setting.
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
A 4-20mA I/O Expansion card input configured as an alarm is below its Low
Setpoint setting.
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
A digital I/O Expansion card input configured as an alarm is
de-energized.
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
An IO Expansion card Alarm input satisfies any of the following:
1.
4-20mA input configured in Bleed Valve Proof of Open mode.
2.
High setpoint is less than the low setpoint plus the deadband.
3.
Digital input configured in any of the following modes:
-
Appliance Firing Rate
-
FARC Air/Fuel/Aux
-
O
Sensor
2
-
Secondary PID
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
The I/O Expansion card input configured as a Firing Rate input is not
reading a valid 4-20mA signal.
* This alarm can only set when Manual Override setting is Disabled
An I/O Expansion card input configured as a FARC position feedback input
is unsatisfied for the duration of the Request Purge Position state.
An I/O Expansion card input configured as a FARC position feedback input
is unsatisfied for the duration of the Request Pilot Position state.
An I/O Expansion card input configured as a FARC position feedback input
is unsatisfied for the duration of the Request Light Off Position Error
timeout during the Pilot state.
The cross limit error exceeds the configured Cross Limit Error setting.
The difference between the requested and actual position of the FARC fuel
actuator exceeds the configured position error threshold.
The difference between the requested and actual position of the FARC air
actuator exceeds the configured position error threshold.
PF3100 Product Manual
Description
DOC-001149 v8.0
186