5.14.3 SYSTEM BEHAVIOR – LEVEL/FLOW INPUT
Configuration Details
Input Mode: Dry Contact
Level/Flow Restart: Disabled
Input Mode: Dry Contact
Level/Flow Restart: Enabled
Input Mode: 4-20 Input
Level/Flow Restart: Any
Input Mode: 4-20 Input
Level/Flow Restart: Disabled
Input Mode: 4-20 Input
Level/Flow Restart: Enabled
1
The appliance Level/Flow input is energized when the first communicating Local Level/Flow input is energized.
2
The appliance Level/Flow input is de-energized when the first communicating Local Level/Flow input is de-energized.
3
The appliance Level/Flow input is out of range when all Local Level/Flow inputs are out of range.
4
The appliance Level/Flow input is tripped when the first communicating Local Level/Flow input is tripped.
5
When Main Permissive Masking setting is Enabled and there is a main permissive alert present on the controller, the level
wait is hidden and the controller remains in its current state.
The following is for applications that have multiple Level/Flow devices monitoring a single Level/Flow
input (i.e., Level/Flow Sharing):
Warning - Level/Flow input redundancy is supported for hardware redundancy only (i.e., the system
!
continues to run if a Level/Flow input loses communication with the appliance or goes out of range,
but the Level/Flow input state is determined by a single input only). The input state of the Level/Flow
input is determined by the first Local Level/Flow input to establish communication with the appliance
only.
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Scenario
Controller State
Input State
Energized
Any
De-energized
Any
Energized
Any stopped state
De-energized
Any running state
De-energized
Out of Range
Any
High Trip
Any
Low Trip
Any stopped state
Low Trip
Any running state
Low Trip
State
Controller Alerts
Transition
1
No effect
N/A
2
Lockout/Alarm
Level/Flow Contact Open alarm
1
No effect
N/A
2
No effect
Level/Flow Contact Open wait
2
Waiting
5
Level/Flow Contact Open wait
3
Lockout/Alarm
Level/Flow Range Error alarm
4
No effect
High Level/Flow warning
4
Lockout/Alarm
Low Level/Flow alarm
4
No effect
Low Level/Flow wait
Waiting
Low Level/Flow wait
4
5
PF3100 Product Manual
DOC-001149 v8.0
5
5
5
5
37