7.3

REQUIRED UV FLAME SCANNER INPUTS

7.3.1
DETAILS
Terminals
Name
Type
7.3.2
INTENDED FIELD DEVICE CONNECTIONS
Field Device
UV flame scanner - Fireye
65UV5 or equivalent
7.3.3
SYSTEM BEHAVIOR – UV FLAME DETECTION
Scenario
Flame On
Fault Input
Input
Energized
Any
De-energized Any
Energized
De-energized De-energized Fault
Any
Energized
De-energized Energized
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
8 & 9, 12, 15
Fault, Flame On, Flame Off
Digital Inputs
Configuration Requirements
Pilot Wizard – Follow on-screen instructions to
configure card
Controller
Flame Off
Interpretation
Input
Any
No fault
Any
Fault
Energized
Fault
De-energized Flame detected
Flame not detected
6
7
8
Earth GND
5
Ignition
4
Enable
3
Contact
N.O. SPST
2
120 VAC/DC,
1
80mA max
PF3102-01
UV Pilot Card
v1.0
Connection Diagrams
UV Flame Scanner Wiring
State
Controller Alerts
Transition
No effect
N/A
Lockout/Alarm UV Flame Detect Fault alarm
Lockout/Alarm UV Flame Detect Mismatch alarm
Lockout/Alarm UV Flame Detect Mismatch alarm
Refer to
Operating Sequence
PF3100 Product Manual
DOC-001149 v8.0
Signal Out Termination
Ground
Floating
9
10 11
12
13
14
15
16 17 18 19
DRY
12V
24V
PF3102-01
PWR Out
XX:00:00:00:XX:XX
Mode
139750
Reset
2021-12-31
v1.0.x
20 - PFRN
section for behavior
52