5.8.3
AUXILIARY OUTPUT POSITION BY CONTROLLER STATE – PID CONTROL
4-20 Aux
Out Mode
FARC Enable
Setting
setting
Disabled
Any
Disabled
PID
Control
Enabled
Disabled
Appliance
Firing Rate
Enabled
5.8.4
AUXILIARY OUTPUT BEHAVIOR BY CONTROLLER STATE – INPUT ECHO
4-20 Aux Out Mode Setting
Process Temp Echo
Fuel Pressure Echo
Level/Flow Echo
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
-
-
-
-
-
Purge Position
Off Position
Purge Position
Off Position
Aux Out Behavior
Temperature input value
is echoed out on the Aux
output as a 4-20mA signal
mapped against the
configured High Temp
setpoint.
BMS input value is echoes
out on the Aux output as
an identical 4-20mA signal
-
-
-
-
-
-
Purge
Pilot
-
-
-
Position
Position
Purge Position Pilot Position
Purge
Pilot
-
-
-
Position
Position
Purge Position Pilot Position
Example
Controller Settings > Process Control > Process Temp Control
High Temp SP:
100 °
4mA output signal corresponds to a reading of 0 °
20mA output signal corresponds to a reading of
A temperature reading of 50 °, in this case, is represented as a
12mA Aux output signal.
An input of 12mA is represented as an identical 12mA Aux
output signal.
PF3100 Product Manual
DOC-001149 v8.0
-
-
-
-
-
-
-
Variable
-
position
between
Minimum and
-
Light
100% per PID
Off
algorithm
-
Variable
-
position
between
-
Minimum and
Light
100% per firing
Off
rate input
100 °
-