ProFire PF3100 Product Manual page 144

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

16.10.1.4
BMS PID
Setting
Proportional Band
Integral Time
Derivative Time
Sample Time
Integral Reset Range
PID Deadband Primary
Rate Limit Primary
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Default
Options
10 °C
0.1 °C – 999.9 °C
18 °F
0.2 °F – 1799.8 °F
4 min
0 min – 999.9 min
0 min
0 min – 999.9 min
1 s
0.1 s – 99999 s
5 °C
0 °C - 1350 °C
9 °F
0 °F - 2430 °F
0 °C
0 °C – 10 °C
0 °F
0 °F – 18 °F
100%/s
1 %/s – 100 %/s
PF3100 Product Manual
Description
Specifies the proportional term used
by the primary PID algorithm.
Specifies the integral term used by the
primary PID algorithm.
Specifies the derivative term used by
the primary PID algorithm.
Specifies the time between samples for
the primary PID algorithm.
Specifies the range above and below
the Process Setpoint within which the
primary PID integral error
accumulates.
Specifies the primary PID deadband
applied to limit fluctuation between
states when the primary process
temperature is near configured
setpoints.
Specifies the maximum rate of change
of the BMS Controller Aux output
during primary PID control.
DOC-001149 v8.0
144