ProFire PF3100 Product Manual page 31

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

5.11.3 SYSTEM BEHAVIOR – AUX IN PROOF OF LOW FIRE
Controller State
Energized
Pilot or
Incinerate No Assist
De-energized
Any other state
Any
5.11.4 SYSTEM BEHAVIOR – AUX IN PROOF OF CLOSURE 2
Incinerator Enable
Controller State
Any
Any non-main state
Disabled
Any main fuel state
Low Fire
Enabled
Incinerate
Incinerator No Assist
5.11.5 SYSTEM BEHAVIOR – AUX IN PROOF OF PILOT
Pilot Off Mode
Controller State
Setting
Any non-fuel state
Off at setpoint or
Follow Main
Any fuel state
Any non-fuel state
Off after main on
Pilot
Any main fuel state
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Scenario
Aux Input state
Scenario
Aux Input State
Energized
De-energized
Energized
De-energized
Energized
De-energized
Energized
De-energized
Energized
De-energized
Scenario
Aux Input State
Energized
De-energized
Energized
De-energized
Energized
De-energized
Energized
De-energized
Energized
De-energized
State transition
No effect
N/A
Lockout
POLF Contact Open alarm
No effect
N/A
State Transition
Controller Alerts
No effect
N/A
Lockout/Alarm
POC2 Contact Open alarm
No effect
POC2 Contact Failed to Open warning
No effect
N/A
No effect
N/A
Lockout
POC2 Contact Open alarm
No effect
POC2 Contact Failed to Open warning
No effect
N/A
No effect
POC2 Contact Failed to Open warning
No effect
N/A
State Transition
Controller Alerts
No effect
N/A
Lockout/Alarm
POP Contact Open alarm
No effect
POP Contact Failed to Open warning
No effect
N/A
No effect
N/A
Lockout/Alarm
POP Contact Open alarm
No effect
POP Contact Failed to Open warning
No effect
N/A
No effect
N/A
Lockout
POP Contact Open Alarm
PF3100 Product Manual
DOC-001149 v8.0
Controller Alerts