ProFire PF3100 Product Manual page 181

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

Code
Alert Name
UI/Modbus
SSV1 Solenoid Error
1017
18
* Alarm 1021 has the same name
SSV2 Solenoid Error
1018
19
* Alarm 1022 has the same name
HF Solenoid Error
1019
20
* Alarm 1023 has the same name
Pilot Solenoid Error
1020
21
* Alarm 1016 has the same name
SSV1 Solenoid Error
1021
22
* Alarm 1017 has the same name
SSV2 Solenoid Error
1022
23
* Alarm 1018 has the same name
HF Solenoid Error
1023
24
* Alarm 1019 has the same name
1024
25
Low Voltage
1025
26
High Voltage
1026
27
Pilot Module Comm Error
1027
28
Incomplete Commissioning
1028
29
Cross Compare Failure
1029
30
Cross Compare Packet Timeout
1030
31
Factory Calibration Error
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
A wiring or hardware error is detected on the SSV1- terminal (terminal 10)
of the BMS Controller card.
A wiring or hardware error is detected on the SSV2- terminal (terminal 8) of
the BMS Controller card.
A wiring or hardware error is detected on the HFV- terminal (terminal 6) of
the BMS Controller card.
A wiring or hardware error is detected on the Pilot+ terminal (terminal 13)
of the BMS Controller card.
A wiring or hardware error is detected on the SSV1+ terminal (terminal 11)
of the BMS Controller card.
A wiring or hardware error is detected on the SSV2+ terminal (terminal 9)
of the BMS Controller card.
A wiring or hardware error is detected on the HFV+ terminal (terminal 7) of
the BMS Controller card.
Any Mode: Temperature or Pilot card voltage is below 32V
12V Mode: BMS Controller card input voltage is below 9.6V
24V Mode: BMS Controller card input voltage is below 19.2V
1
This alarm can only be present when the Low Voltage Restart setting is
set to Disabled.
2
Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
Any Mode: Temperature or Pilot card voltage is above 40V
12V Mode: BMS Controller card input voltage is above 16.8V
24V Mode: BMS Controller card input voltage is above 33.6V
1
This alarm can only be present when the High Voltage Restart setting is
set to Disabled.
2
Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
PFRN connection between the BMS controller card and a Pilot card has
been lost and the Minimum Pilots Running requirement is not satisfied.
This alarm sets immediately when the Comm Loss Restart setting is
1
Disabled and sets after 5 minutes when the Comm Loss Restart setting is
Enabled.
2
Pressing the OK button on the alert text opens a dialog that identifies the
offending card.
The commissioning date setting has not been set.
Internal BMS Controller card fault.
Internal BMS Controller card fault.
Internal BMS Controller card fault.
* This alarm can only be present when the Factory Cal Error Mode setting
(BMS Settings > Calibration > BMS) is set to Alarm.
PF3100 Product Manual
Description
1
1
Contact
Profire.
Contact
Profire.
Contact
Profire.
DOC-001149 v8.0
.
.
1
.
1
.
1
1
181