ProFire PF3100 Product Manual page 143

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

16.10.1.2
OTHER TEMPERATURES
The Process Temp Control settings above pertain only to the primary process temperature input. The Logical
Input Configuration link shown in the Other Temperatures menu can be used to view the settings of all configured
temperatures. Changes to the settings must be made in the
16.10.1.3
TIMING
Setting
Pre Purge Time
Purge Time
Pilot to Main Delay
Low to High Fire Delay
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Default
Options
60 s
10s – 900 s
60 s
10 s - 900 s
15 s
5 s - 600 s
30 s
30 s - 600 s
Temperature
Wizard.
Description
Specifies the duration of the Proven Pre-Purge
controller state, when applicable.
Specifies the time for which the system purges
upon power up and following a lockout.
Specifies the time for which the system remains
in the Pilot state before proceeding to light off
the main valves.
Specifies the time for which the system remains
in the Low Fire state before proceeding to High
Fire.
PF3100 Product Manual
DOC-001149 v8.0
143