Code
2009
IO Expansion Input Invalid
IO Expansion Analog Input
2010
High
2011
IO Expansion Analog Input Low
IO Expansion Digital Input
2012
Open
2013
Level/Flow Contact Open
IO Expansion Configuration
2014
Error
2015
Low Heat Standby
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Alert Name
An I/O Expansion card input configured as a wait is not reading a valid
input signal.
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
A 4-20mA I/O Expansion card input configured as a wait is above its High
Setpoint setting.
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
A 4-20mA I/O Expansion card input configured as a wait is below its Low
Setpoint setting.
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
A digital I/O Expansion card input configured as a wait is
de-energized.
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
4-20 Mode: This alarm cannot be set.
Dry Contact Mode: The Appliance or Controller Level/Flow input is de-
energized.
* This wait can only be present when the Level/Flow Restart setting is set
to Enabled.
An IO Expansion card Wait input satisfies any of the following:
* Pressing the OK button on the alert text opens a dialog that identifies the
offending card and input.
Low Heat Standby Mode is configured as a Wait, the Controller is in the PID
Control State, and one of the following conditions is present for the
duration of the configured Low Heat Standby Delay:
Description
1.
4-20mA input configured in Bleed Valve Proof of Open mode.
2.
High setpoint is less than the low setpoint plus the deadband.
3.
Digital input configured in any of the following modes:
-
Appliance Firing Rate
-
FARC Air/Fuel/Aux
-
O
Sensor
2
-
Secondary PID
1.
Basic PID: Firing Rate is at the configured Minimum Firing Rate
and the Process Temperature is greater than the Process
Setpoint.
2.
Cascaded PID: PID Process Setpoint is at the configured Primary
Setpoint Min setting and the Process Temperature is greater than
the Primary Setpoint Min setting and Secondary Input is greater
than the Secondary Process Setpoint minus Deadband.
PF3100 Product Manual
DOC-001149 v8.0
191