Pfrn Ports - ProFire PF3100 Product Manual

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

10.3 PFRN PORTS

10.3.1 DETAILS
Name
Type
10.3.2 INTENDED FIELD DEVICE CONNECTIONS
Field Device
PF3101-00 BMS card PFRN
Controller Network port
PF3101-00 BMS card PFRN I/O
Network port
* Network cards cannot be connected to PFRN Controller Network port(s) and PFRN I/O Network port(s) at the same time.
Separate cards must be used when expansion of both the Controller network and I/O network is required.
10.3.3 SYSTEM BEHAVIOR – DIAGNOSTIC LEDS
Name
Color
Pwr
Blue
Link
Green
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Port 1, Port 2, Port 3, Port 4 & Port 5
PFRN bus expansion port (Controller or I/O
network)
Configuration Requirements
N/A
N/A
LED Behavior
Interpretation
Off
Port has no power
On – Solid
Port has power
Port has intermittent
On – Flickering
power
Port is not
Off
communicating
On – Solid
Port is communicating
normally
On – Flickering
PF3100 Product Manual
Reset
Connection Diagrams
PFRN Connector Wiring
UI PFRN Connection Options
PFRN Connector Wiring
I/O Card PFRN Wiring Options
Issue/Corrective Action
No Power – Make sure Network card has
power supplied to Power Input
terminals.
Wiring fault – Check PFRN wire
terminations at Network card and
connected card.
Hardware fault –
Contact Profire
replacement.
N/A
Wiring fault – Check PFRN wire
terminations at Network card and
connected card.
Hardware fault –
Contact Profire
replacement.
No PFRN Communication – Cycle power
to system and check PFRN wire
terminations at Network card and
connected card.
N/A