Controller Power Input - ProFire PF3100 Product Manual

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

5.2

CONTROLLER POWER INPUT

5.2.1
DETAILS
Terminals
Name
Type
Fuse
5.2.2
INTENDED FIELD DEVICE CONNECTIONS
Field Device
12V Power Supply
24V Power Supply
5.2.3
VOLTAGE ALERT BEHAVIOR – 12V MODE
System Voltage
Below 9.6V *
Between 9.6V and 9.9V *
Between 9.9V and 16.1V *
Between 16.1V and 16.8V * Any
Above 16.8V *
* All listed voltage thresholds are +/- 1.0 V
5.2.4
VOLTAGE ALERT BEHAVIOR – 24V MODE
System Voltage
Below 19.2V *
Between 19.2V and 19.9V * Any
Between 19.9V and 33.1V * Any
Between 33.1V and 33.6V * Any
Above 33.6V *
* All listed voltage thresholds are +/- 1.0 V
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
1, 2 & 3
Power Input
BMS power input
10A ceramic,
Contact Profire
Configuration Requirements
Controller Settings > Setup > System Voltage
Controller Voltage: 12V
Voltage Restart: As desired
Controller Settings > Setup > System Voltage
Controller Voltage: 24V
Voltage Restart: As desired
Scenario
Low Voltage
High Voltage
Restart
Restart
Enabled
Any
Disabled
Any
Any
Any
Any
Any
Any
Any
Enabled
Any
Disabled
Scenario
Low Voltage
High Voltage
Restart
Restart
Enabled
Any
Disabled
Any
Any
Any
Any
Any
Enabled
Any
Disabled
for replacements
Controller State
Any running state
Any stopped state
Any running state
Any stopped state
Any
Any
Any
Any running state
Any stopped state
Any running state
Any stopped state
Controller State
Any running state
Any stopped state
Any running state
Any stopped state
Any
Any
Any
Any running state
Any stopped state
Any running state
Any stopped state
PF3100 Product Manual
DOC-001149 v8.0
PFRN Controller Network
PFRN IO Network
33 – Ignition
Switch
PF3101-00
BMS Controller
R un Ign it e O n
V1.3
35 – License Key
PF3101-00
XX: 00:00: 00:XX: XX
## ## ##
Push Tabs
YYYY-MM-DD
To Remove Key
V# .#. #
27
26
25
24
23
22
21
20
19
18
17
16
15
14
13 12
11 10
9
8
4-20mA / Dry
4-20mA
12/24V
Contact Inputs
Dry Contact Inputs
Powered Outputs
Connection Diagrams
Power Input Wiring
State
Controller Alerts
Transition
Waiting
Low Voltage Wait
No effect
Low Voltage Wait
Lockout
Low Voltage Alarm
Alarm
Low Voltage Alarm
No effect
Low Voltage Warning
No effect
N/A
No effect
High Voltage Warning
Waiting
High Voltage Wait
No effect
High Voltage Wait
Lockout
High Voltage Alarm
Alarm
High Voltage Alarm
State
Controller Alerts
Transition
Waiting
Low Voltage Wait
No effect
Low Voltage Wait
Lockout
Low Voltage Alarm
Alarm
Low Voltage Alarm
No effect
Low Voltage Warning
No effect
N/A
No effect
High Voltage Warning
Waiting
High Voltage Wait
No effect
High Voltage Wait
Lockout
High Voltage Alarm
Alarm
High Voltage Alarm
10A
Fuse
7
6
5
4
3
2
1
STATUS
SPST
NO
80mA
Power Input
120 VAC/
120 VDC
MAX
Relay Output
20

Advertisement

Table of Contents
loading