20 ALERT CODES

20.1 ALARMS

Alarms are alerts that prevent a controller from entering any running state. The table below describes each alarm
and indicates the unique shutdown codes used to identify them both over Modbus and on the UI.
Code
Alert Name
UI/Modbus
1000
1
Pilot Flame Detected While Off
1001
2
Main Flame Detected While Off
1002
3
POC Contact Open
1003
4
POLF Contact Open
1004
5
POC2 Contact Open
1005
6
POP Contact Open
1006
7
Level/Flow Contact Open
1007
8
Low Level/Flow
1008
9
Fuel Pressure Contact Open
1009
10
Low Fuel Pressure
1010
11
Low Fuel Pressure Dry Contact
1011
12
ESD Contact Open
Primary Process Temperature
1012
13
High ESD
1013
14
Incompatible Firmware
1014
15
Reserved
1015
16
Reserved
Pilot Solenoid Error
1016
17
* Alarm 1020 has the same name
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Pilot flame is detected before the pilot ignition sequence is initiated.
Main flame is detected before the pilot ignition sequence is initiated.
The BMS Controller Proof of Closure input is de-energized when it is
expected to be energized.
The BMS Controller Aux input (configured as a Proof of Low Fire input) is
de-energized when in Pilot state or Incinerate No Assist state.
The BMS Controller Aux input (configured as a Proof of Closure 2 input) is
de-energized when it is expected to be energized.
The BMS Controller Aux input (configured as a Proof of Pilot input) is de-
energized when it is expected to be energized.
4-20 Mode: This alarm cannot be set.
Dry Contact Mode: The Appliance or Controller Level/Flow input is de-
energized.
* This alarm can only be present when the Level/Flow Restart setting is set
to Disabled.
4-20 Mode: The BMS Appliance or Controller Level/Flow input reading is
less than Low Level/Flow SP setting.
Dry Contact Mode: This alarm cannot be set.
* This alarm can only be present when the Low Level/Flow Restart setting
is set to Disabled.
4-20 Mode: This alarm cannot be set.
Dry Contact Mode: The BMS Controller Pressure input is de-energized.
Dry Contact High Press Mode: This alarm cannot be set.
4-20 Mode: BMS Controller Pressure input reading is less than its Low
Pressure SP setting.
Dry Contact Mode: This alarm cannot be set.
Dry Contact High Press Mode: This alarm cannot be set
* This alarm can only be present when the Low Fuel Pressure Restart
setting is set to Disabled.
The Aux Input (configured as a Low Pressure input) is de-energized.
* This alarm can only be present when the Low Fuel Pressure Restart
setting is set to Disabled.
The ESD (Emergency Shutdown) input is de-energized.
Process temperature input reading is above its High Temp SP setting.
A card has a different firmware version than the BMS Controller to which it
is connected.
A wiring or hardware error is detected on the Pilot- terminal (terminal 12)
of the BMS Controller card.
PF3100 Product Manual
Description
DOC-001149 v8.0
180