13.11.3 INCINERATE NO ASSIST STATE
13.11.3.1
SAFETY OUTPUT BEHAVIOR – INCINERATE NO ASSIST STATE
Card
PF3101-00 BMS Controller card
PF3102-00 Ion Pilot card
PF3102-01 UV Pilot card
1
De-energized when Pilot Off Mode is set to Off After Main On
2
Energized under reignition conditions in accordance with configured Pilot Relight Mode and Pilot Relight Timeout settings
(Controller Settings > Outputs > Ignition).
13.11.3.2
TRANSITIONS TO THE INCINERATE NO ASSIST STATE
From
Scenario
Process temperature is above its configured
Incinerate
Assist Gas Off Setpoint
13.11.3.3
TRANSITIONS FROM THE INCINERATE NO ASSIST STATE
To
Scenario
Any
Lockout
Controller stopped by user
Flame loss
Any
Any
Waiting
Flame loss
Process temperature is above its configured
Waste Gas Off setpoint
Any
Pilot
Process temperature is above its configured
Waste Gas Off setpoint
Process temperature is below its configured
Incinerate
Assist Gas Off Setpoint
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Output
Pilot
SSV1
SSV2
Valve
Coil
Ignition Enable
Condition
No alarm or wait or main permissive conditions present
Condition
Alarm condition present
Any
Relight Attempts setting exceeded
Wait condition present
Main permissive condition present, AND
Pilot Off Mode setting is set to Off after Main On or Follow
Main
Relight Attempts setting has not been exceeded
Pilot Off Mode setting is set to Off after Main On or Follow
Main
Main permissive condition present, AND
Pilot Off Mode setting is set to Disabled or Off at Setpoint
Pilot Off Mode setting is set to Disabled or Off at Setpoint
No alarm or wait or main permissive conditions present
PF3100 Product Manual
DOC-001149 v8.0
Output State
Energized
1
De-energized
Energized
Energized
1
De-energized
2
Open
2
105