ProFire PF3100 Product Manual page 188

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

Code
Alert Name
UI/Modbus
Cross Limiting Enabled on
1124
125
Invalid Curve
No Position Feedback On Cross
1125
126
Limited Channel
1126
127
FARC Settings Error
1127
128
FARC Requires Proof of Airflow
1128
129
FARC Requires Forced Draft Fan
1129
130
FARC Requires Low Fire
1130
131
FARC Requires Aux Out
FARC Table Requires
1131
132
Commissioning
FARC Fuel and Air Channels not
1132
133
Assigned
FARC Air Control Output
1133
134
Configuration Error
1134
135
FARC Light Off Firing Rate Error
1135
136
FARC Settings Out of Range
FARC Aux 1 Channel Position
1136
137
Error
FARC Aux 2 Channel Position
1137
138
Error
FARC Aux 3 Channel Position
1138
139
Error
1139
140
FARC Feedback Missing
1140
141
FARC Redundant Inputs
Bleed Valve Proof of Open
1141
142
Configuration Error
1142
143
O
Sensor Configuration Error
2
FARC Output Configuration
1143
144
Error
Appliance Firing Rate
1144
145
Configuration Error
Logical Temperature Input
1145
146
Name Collision
Proof of Airflow Configuration
1146
147
Error
TC Flame Detect Requires a
1147
148
4-20 Input
O
Trim Enabled Without Stack
2
1148
149
Input
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Cross limiting is enabled on a curve that contains an inflection point.
Cross limiting is enabled on a FARC channel that does not have a
corresponding position feedback input configured.
Fuel or Air FARC channel settings have been improperly configured
through a Settings Restore with a corrupted settings file.
FARC is enabled with no proof of airflow input configured.
FARC is enabled and HFV Output Mode settings is not set to Forced Draft
Fan.
FARC is enabled and Low Fire Mode setting is set to Disabled.
FARC is enabled and Aux Out Mode settings is not set to PID Control or
Appliance Firing Rate.
FARC is enabled and the currently selected FARC curve is not
commissioned.
FARC is enabled with no corresponding Fuel or Air channels configured.
FARC is enabled and there is:
-
More than one FARC Air Output configured, or
-
Less than one FARC Air Output configured.
FARC is enabled and the Light Off Firing Rate setting is less than the
Minimum Firing Rate setting.
FARC Position error, cross limit error or FARC mode settings are configured
with invalid values.
The difference between the requested and actual position of the FARC Aux
1 channel actuator exceeds the configured position error threshold.
The difference between the requested and actual position of the FARC Aux
2 channel actuator exceeds the configured position error threshold.
The difference between the requested and actual position of the FARC Aux
3 channel actuator exceeds the configured position error threshold.
FARC channel Position Feedback Setting is enabled with no corresponding
feedback input configured.
A FARC input is assigned to multiple IO Expansion input slots.
There is more than one Bleed Valve Input configured or settings have been
configured with invalid values.
There is more than one O
sensor input configured, or settings have been
2
configured with invalid values.
There are multiple outputs configured for a single FARC channel.
There is more than one Firing Rate input configured or settings have been
configured with invalid values.
Two or more configured temperature inputs have the same name.
A single BMS has a Proof of Airflow input configured on both its Aux Input
and its I/O Expansion card, or there is more than one Local Proof of Airflow
logical input created in the I/O Wizard.
TC Flame Detect is enabled and Ion Aux In / LEL Input is not configured as
a 4-20mA input or TC Flame Detect is enabled with a UV Pilot card.
O
Sensor Warmup Mode setting is configured as Stack Temp with no valid
2
temperature input assigned.
PF3100 Product Manual
Description
DOC-001149 v8.0
188