Field Device/Application
Oxygen sensor
4-20mA transmitter with
separate low trip and high
trip behavior
* This application is not
safety rated. Separate
devices must be used to
maintain safety rating.
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Configuration Requirements
I/O Wizard > Add Inputs Tab
Input Type: O
Sensor Reading
2
Name: As per equipment tag
Units: As desired
I/O Wizard > I/O Modules Tab
Input 1-4: As per field wiring
All other settings: As desired
FARC / O
Trim Wizard > O
2
2
All Settings: As per safety design documentation
FARC / O
Trim Wizard > O
2
2
Configure O
Curve Menu
2
Configure O
curve in accordance with safety
2
design documentation and O
I/O Wizard > Add Inputs Tab
Input 1:
Input Type: As per device type
Signal Type: 4-20
Input Mode: Desired high trip behavior
Low Setpoint: Set to transmitter 4mA position
High Trip Setpoint: As desired
All other settings: As desired
Input 2:
Input Type: Same as above
Signal Type: 4-20
Input Mode: Desired low trip behavior
Low Setpoint: As desired
High Trip Setpoint: Set to transmitter 20mA
position
All other settings: As desired
I/O Wizard > I/O Modules Tab
Input 1: Assign Input 1 from above
Input 2: Assign Input 2 from above
All other settings: As desired
PF3113 Hardware Configuration
DIP Switch 1: Floating
DIP Switch 2: Ground
Connection Diagrams
Loop Powered Transmitter
Self Powered Transmitter
Trim Tab
Trim Tab >
Trim profile.
2
Single Transmitter to Multiple Inputs