ProFire PF3100 Product Manual page 77

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

Field Device/Application
FARC valve position feedback
input
FARC air position feedback
input
FARC Aux channel position
feedback input
Bleed valve proof of open
switch(es)
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Configuration Requirements
I/O Wizard > Add Inputs Tab
Input Type: FARC Valve Position
All other settings: Ignored
I/O Wizard > I/O Modules Tab
Input 1-4: As per field wiring
All other settings: As desired
FARC / O
Trim Wizard > General Tab
2
FARC Enable: Enabled
All other settings: As required per safety design
documentation
I/O Wizard > Add Inputs Tab
Input Type: FARC Air Position
All other settings: Ignored
I/O Wizard > I/O Modules Tab
Input 1-4: As per field wiring
4-20 Output: Air Position Controlled by FARC
All other settings: As desired
FARC / O
Trim Wizard > General Tab
2
FARC Enable: Enabled
All other settings: As required per safety design
documentation
I/O Wizard > Add Inputs Tab
Input Type: CHx Feedback Position
All other settings: Ignored
I/O Wizard > I/O Modules Tab
Input 1-4: As per field wiring
4-20 Output: CHx Position Controlled by FARC
All other settings: As desired
FARC / O
Trim Wizard > General Tab
2
FARC Enable: Enabled
All other settings: As required per safety design
documentation
FARC /Or Trim Wizard > Channels Tab >
Channel Configuration Menu
Position Feedback: Select appropriate channel
I/O Wizard > Add Inputs Tab
Input Type: Bleed Valve Proof of Open
All other settings: Ignored
I/O Wizard > I/O Modules Tab *
Input 1-4: As per field wiring
All other settings: As desired
* Input applies only to the BMS controller card
to which it is connected (via I/O Expansion
card). Multi-BMS applications require each
BMS to have a dedicated I/O Expansion card
connected with the single Bleed Valve Proof of
Open logical input assigned.
PF3100 Product Manual
Connection Diagrams
Loop Powered Transmitter
Self Powered Transmitter
Loop Powered Transmitter
Self Powered Transmitter
Loop Powered Transmitter
Self Powered Transmitter
Digital Input – Dry Contact
Digital Input – Wet Contact
DOC-001149 v8.0