Ma Output; Terminals 5, 6; Intended Field Device Connections - ProFire PF3100 Product Manual

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

12.4 4-20 mA OUTPUT

12.4.1 DETAILS
Terminals
6 & 7
Name
4-20mA Out
Type
4-20mA powered output

12.4.2 INTENDED FIELD DEVICE CONNECTIONS

The PF3113-00 I/O Expansion card 4-20mA output is not safety rated and cannot be used for safety critical
functions.
Field Device
Configuration Requirements
I/O Wizard > Add Inputs Tab
Create up to four 4-20mA inputs as desired
I/O Wizard > I/O Modules Tab
Inputs 1-4: Assign as per field wiring
4-20 Output: PID Output Controlled by 4-20mA Input
Proportional
Select I/O Card 4-20 Inputs: Up to four as desired
actuator
All selected inputs are averaged to determine the input reading used by the PID output.
controlled by
I/O Wizard > Configure PID Parameters Dialog
PID control on
Setpoint: As desired
4-20mA input(s)
PID Parameters: As desired
Direction: As desired
Mode: Auto
System Stop Output: As desired/required
Output Limits: As desired/required
Temperature Wizard > Create Inputs Tab
Create up to four temperature inputs as desired
* Note that these inputs must be created in the Temperature Wizard
rather than in the I/O Wizard
I/O Wizard > I/O Modules Tab
Inputs 1-4: Assign as per field wiring
Proportional
4-20 Output: PID Output Controlled by TC Input
actuator
controlled by
Select Temperature Inputs: Up to four as desired
PID control on
All selected inputs are averaged to determine the input reading used by the PID output.
I/O Wizard > Configure PID Parameters Dialog
thermocouple
input(s)
Setpoint: As desired
PID Parameters: As desired
Direction: As desired
Mode: Auto
System Stop Output: As desired/required
Output Limits: As desired/required
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
PF3100 Product Manual
DOC-001149 v8.0
Signal Out Termination
Ground
Floating
6
7
8
9 10 11 12 13
14 15 16 17 18 19
1 2 3 4
Input #
Earth GND
6
7
8 9 10
11 12 13
14 15 16
17 18 19
5
4
N.O. Dry
Contact
3
Ou t
2
N.C. Dry
Contact
1
Ou t
4-20mA
Input 1
Input 2
Input 3
Input 4
Ou t
SPST 120 VAC/DC, 80mA max
PF3113-00
XX:00:00:00:XX:XX
PF3113-00
139750
Reset
IO Expansion Card
2021-12-31
V2.0
v2.0.x
20 - PFRN
Connection Diagrams
Proportional Valve/Actuator
Wiring
Proportional Valve/Actuator
Wiring
12V
24V
PWR Out
Mode
73

Advertisement

Table of Contents
loading

Table of Contents