16.10.1.6
ADVANCED PID CONFIG
Setting
Default
Integral
Enabled
Jacketing
Cascaded PID
Disabled
PID Staging
Disabled
Mode
PID Ramp
5 s
Time
Primary
90 °C
Setpoint Max
194 °F
Primary
0 °C
Setpoint Min
32 °F
Secondary
90 °C
Setpoint Max
194 °F
Secondary
0 °C
Setpoint Min
32 °F
Secondary
-
Input
Staging Input
-
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
Options
Description
PID integral error does not accumulate when the PID output is
Enabled
operating at 100% or at its configured Minimum Position.
PID integral error continues to accumulate when the PID output is
Disabled
operating at 100% or at its configured Minimum Position.
Enabled
Cascaded PID is enabled
Disabled
Cascaded PID is disabled
Disabled
The system controls based on the Primary process temperature only.
The system switches from primary to secondary input control when the
High Input
configured Staging Input is above its
The system switches from primary to secondary input control when the
Low Input
configured Staging Input is below its
The system switches from primary to secondary input control when the
Primary In Range
primary temp is above the configured Primary Setpoint Min setting.
The system switches from primary to secondary input control when the
Secondary In Range
configured secondary temperature is between the configured
Secondary Setpoint Min and Secondary Setpoint Max settings below.
The system switches from primary to secondary input control when
Primary AND
both the primary and secondary temperatures are between their
Secondary in Range
configured Setpoint Min and Setpoint Max settings below.
The system switches from primary to secondary input control when
Primary OR
either the primary or secondary temperature is between its configured
Secondary in Range
Setpoint Min and Setpoint Max settings below.
Specifies the time the BMS controller Aux output takes to ramp to 100%
0 s – 60 s
upon entry into the PID control state.
Specifies the maximum value to which the primary process setpoint
0 °C - 1350 °C
can be changed by the system.
32 °F - 2462 °C
* Must be set between the configured
Specifies the minimum value to which the primary process setpoint can
0 °C - 1350 °C
be changed by the system.
32 °F - 2462 °C
* Must be set between the configured
Specifies the maximum value to which the secondary process setpoint
0 °C - 1350 °C
can be changed by the system.
32 °F - 2462 °C
* Must be set between the configured
Specifies the minimum value to which the secondary process setpoint
0 °C - 1350 °C
can be changed by the system.
32 °F - 2462 °C
* Must be set between the configured
Any temperature or
Secondary PID I/O
Specifies the input used as a secondary PID input.
Expansion Input
Any configured I/O
Specifies the I/O Expansion input used as a staging input
expansion input
PF3100 Product Manual
DOC-001149 v8.0
High Trip
setpoint.
Low Trip
setpoint.
Process Setpoint
and
Low Fire
Setpoint.
Process Setpoint
and
Low Temp
Process Setpoint
and
Low Fire
Setpoint.
Process Setpoint
and
Low Temp
Setpoint.
Setpoint.
146