Ignition Enable Relay Contact - ProFire PF3100 Product Manual

Hide thumbs Also See for PF3100:
Table of Contents

Advertisement

7.2

IGNITION ENABLE RELAY CONTACT

7.2.1
DETAILS
Terminals
Name
Type
7.2.2
INTENDED FIELD DEVICE CONNECTIONS
Field Device
High Energy Ignition
module via relay
PF3102-03 Pilot Spark card
7.2.3
UV PILOT IGNITION ENABLE RELAY BEHAVIOR BY CONTROLLER STATE
System Configuration
Any
1
E = Energized, D = De-energized
2
Energized under reignition conditions in accordance with configured Pilot Relight Mode and Pilot Relight Timeout settings
(Controller Settings > Outputs > Ignition).
Copyright © 2022, Profire Energy. All rights reserved.
855.PRO.FIRE | PROFIREENERGY.COM
3 & 4
Ignition Enable Dry Contact
Normally open dry contact
Configuration Requirements
Pilot Wizard > Allocate Pilot Tab
Enabled/Disabled: Enabled
Pilot Wizard > Allocate Pilot Tab
Enabled/Disabled: Enabled
D
D
D
Connection Diagrams
UV Pilot High Energy Ignition Wiring
UV Pilot to Spark Card Wiring
D
D
D
D
PF3100 Product Manual
DOC-001149 v8.0
Signal Out Termination
Ground
Floating
6
7
8
9 10 11 12 13
14 15 16 17 18 19
Earth GND
5
Ignition
4
Enable
DRY
3
Contact
N.O. SPST
2
120 VAC/DC,
1
80mA max
PF3102-01
XX:00:00:00:XX:XX
PF3102-01
139750
Reset
UV Pilot Card
2021-12-31
v1.0
v1.0.x
20 - PFRN
E
D
2
D
2
12V
24V
PWR Out
Mode
D
2
51