Metasys N2 Point Database - YASKAWA E7N Technical Manual

Drive/bypass
Table of Contents

Advertisement

Metasys N2 Point Database

Metasys N2 Analog Input (AI) Summary
Object ID
AI 1
AI 2
AI 3
AI 4
AI 5
AI 6
AI 7
AI 8
AI 9
AI 10
AI 11
AI 12
AI 13
AI 14
AI 15
AI 16
AI 17
AI 18
AI 19
AI 20
AI 21
AI 22
AI 23
AI 24
AI 25
AI 26
AI 27
AI 28
AI 29
AI 30
AI 31
AI 32
AI 33
AI 34
AI 35
AI 36
AI 37
AI 38
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com
Table D.9 Metasys N2 Analog Input Summary (E7 to Metasys N2)
Object Name
SPEED REFERENCE
OUTPUT SPEED
OUTPUT CURRENT
kWATT HOUR METER
OUTPUT POWER
DRIVE TEMPERATURE
PI FEEDBACK
AC OUTPUT VOLTAGE
DC BUS VOLTAGE
FAULT CODE
ELAPSED TIME - HOURS
ELAPSED TIME – 10K HOURS
MEGAWATT HOUR METER
DRIVE RATED CURRENT
COMMUNICATION ERROR CODE
PI DEVIATION
PI OUTPUT CAPACITY
PI REFERENCE
LAST FAULT CODE
FREQ REF @ FAULT
OUTPUT FREQ @ FAULT
OUTPUT CURRENT @ FAULT
OUT VOLT REF @ FAULT
DC BUS VOLTS @ FAULT
OUTPUT POWER @ FAULT
INPUT TERM STATUS @ FAULT
OUTPUT TERM STATUS @ FAULT
OPERATION STATUS @ FAULT
ELAPSED OPERATION TIME @ FAULT
MOST RECENT FAULT
2nd MOST RECENT FAULT
3rd MOST RECENT FAULT
4th MOST RECENT FAULT
ELAPSED TIME @ CURRENT FAULT
ELAPSED TIME @ 2nd FAULT
ELAPSED TIME @ 3rd FAULT
ELAPSED TIME @ 4th FAULT
READ PARAMETER DATA
Communications D - 16
Units
E7 Parameter
0.01 Hz
U1-01
0.01 Hz
U1-02
0.1A
U1-03
kWh
0.1kW
U1-08
o
1
C
0.01%
U1-24
0.1VAC
U1-06
1Vdc
U1-07
-
U2-01
1 HOUR
U1-13
10K HOURS
U1-13
MWh
U1-30
A
n9-01
-
U1-39
0.01%
U1-36
0.01%
U1-37
0.01%
U1-38
-
U2-02
0.01Hz
U2-03
0.01Hz
U2-04
0.1A
U2-05
0.1VAC
U2-07
1Vdc
U2-08
0.1Kw
U2-09
-
U2-11
-
U2-12
-
U2-13
1 HOUR
U2-14
-
U3-01
-
U3-02
-
U3-03
-
U3-04
1 HOUR
U3-05
1 HOUR
U3-06
1 HOUR
U3-07
1 HOUR
U3-08
-
-
-
-

Advertisement

Table of Contents
loading