10.2 High-level positioning control execution procedure

Preparation
STEP 1
Refer to Chapter 9
STEP 2
Refer to Section 10.3
STEP 3
Refer to Section 10.4
STEP 4
Refer to Section 10.6
STEP 5
Refer to Chapter 6
STEP 6
Starting the control
Refer to Section 6.5.3
STEP 7
Monitoring the control
Stopping the control
STEP 8
Refer to Section 6.5.6
High-level positioning control is carried out using the following procedure.
Carry out the "major positioning control" setting.
Set the "block start data" corresponding to each
(Note-1)
control
.
( Da. 11 to Da. 14 ) × required data amount
Set the "condition data"
( Da. 15 to Da. 19 and Da.23 to Da.26 ) ×
required data amount
Create a sequence program in which block No. is set in
"
the
Cd. 3 Positioning start No.
(Control data setting)
Create a sequence program in which the "block start
data point No. to be started" (1 to 50) is set in the
" Cd. 4 Positioning starting point No.
Create a sequence program in which the "positioning
start signal" is turned ON by a positioning start command.
Write the sequence programs created in STEP4
to the PLC CPU.
Turn ON the "positioning start command" of
the axis to be started.
Monitor the high-level positioning control.
Stop when control is completed
Control termination
REMARK
(Note-1): Five sets of "block start data (50 points)" and "condition data (10 items)"
corresponding to "block No. 7000 to 7004" are set with GX Works2 or
sequence program.
When those are set with GX Works2 and written to the Simple Motion
module, "7000 to 7004" can be set in "
when the above is set.
Chapter 10 High-Level Positioning Control
(Note-1)
.
(Note-1)
"
"
10 - 6
"High-level positioning control" executes each control
("major positioning control") set in the positioning data
with the designated conditions, so first carry out
preparations so that "major positioning control" can be
executed.
The "block start data" from 1 to 50 points can be set.
Set the "condition data" for designation with the
"block start data". Up to 10 condition data items
can be set.
The Simple Motion module recognizes that the control
is high-level positioning control using "block start data"
by the "7000" designation.
Use GX Works2 to create a sequence program
to execute the "high-level positioning control".
Write the sequence program created in STEP 4 to the
PLC CPU using GX Works2.
Same procedure as for the "major positioning control"
start.
Monitor using GX Works2
.
Same procedure as for the "major positioning control" stop.
Positioning start No.
Cd.3
" on STEP4