CPI Canada Inc.
3B.3.3 Selecting Output Voltages (Cont)
IT IS THE RESPONSIBILITY OF THE INSTALLER TO PROVIDE THE PROPER INTERFACING CIRCUITS TO THE
OPTO COUPLER(S) IN THESE TYPES OF INSTALLATIONS.
For reference, the jumper wire links associated with each of the subject relays is listed below:
RELAY
K1
K2
K3
K4
K6
K8
3B.3.4 Typical Examples
Selected Output Relay
K2 (24 VDC)
K1 (110 VAC)
K4 (24 VDC)
K3 (220 VAC)
K6 (dry contacts)
K12 (24 VDC)
K13 (dry contacts)
K7 (24 VDC)
The previous examples will configure the outputs as shown below:
• K2 when selected will provide 24 VDC to a load at TB1 pins 11 and 12.
• K1 when selected will supply 110 VAC to a load at TB1 pins 1 and 2.
• K4 when selected will supply 24 VDC to a load at TB2 pins 11 and 12.
• K3 when selected will supply 220 VAC to a load at TB2 pins 1 and 2.
• K6 when selected will supply closed contacts at TB3 pins 11 and 12.
• K12 when selected will supply 24 VDC at TB6 pins 1 and 2.
• K13 when selected will supply closed contacts at TB6 pins 11 and 12.
• K7 will supply 24 VDC at TB4 pin 3 for tube 1, or 24 VDC at TB4 pin 2 for tube 2. Ground
reference will be at TB4 pin 1.
Indico 100 Series Service Manual
JUMPER WIRE
JW12
JW9
JW11
JW10
JW14
JW13
Plug and Jumper
JW2: Live Contact
JW1: Live Contact
JW4: Live Contact
JW3: Live Contact
JW5: Dry Contact
JW7: Live Contact 24VDC
JW8: Dry Contact
JW6: Live Contact 24VDC
Ch # 740895-05
Rev. E
System Interfacing
Wire Jumper
(K2) TB11 - 5 to TB8
(K1) TB11 - 4 to TB9
(K4) TB11 - 3 to TB8
(K3) TB11 - 2 to TB10
(K6) TB11 - no connection
N/A
N/A
N/A
Page 3B-9