Nortel DMS-100 Series Maintenance Manual page 662

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

13-14 Routine maintenance procedures
Battery inspection and cleaning
OPAC
(continued)
At the OPAC site
6
7
8
9
10
11
297-8211-550 Standard 05.01 August 1999
WARNING
Possible system damage
You can add or remove battery strings from an active
OPAC. If you perform this action make sure the
battery strings are in the open circuit state from the
MAP terminal. Turn off the associated battery charger
controller (BCC) card NT8X02AB. Connect or
disconnect the battery cables at the back of the
cabinet. After you connect the affected battery
strings, return the battery strings to the load bus one
string at a time.If there is no MAP terminal control,
turn off the BCC before you connect or disconnect any
battery strings..
CAUTION
Possible loss of service during battery replacement
Do not turn off more than one NT8X02 at a time. If
you turn off more than one NT8X02 at a time service
is lost if ac power is interrupted. Turn off BCC0 when
you perform work on battery strings 0, 1, or 2. Turn
off BCC1 when you perform work on battery string 4,
5 or 6.
Turn the appropriate BCC NT8X02 power switch to the OFF position.
Disconnect and remove matched battery string or strings from the affected shelf
or floor area.
Clean the affected areas with baking soda and water. Continue until the
cleaning solution does not foam when you apply the cleaning solution.
Dry all cleaned areas completely and replace the batteries.
Reconnect the battery string or strings.
Turn the BCC NT8X02 power switch to the ON position.