Nortel DMS-100 Series Maintenance Manual page 279

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Clearing an RCLM major alarm
At the MAP terminal
1
If an alarm is audible, silence the alarm. To silence the alarm, type:
>MAPCI;MTC;SIL
and press the Enter key.
2
To access the PM level of the MAP display, type:
>PM
and press the Enter key.
3
To identify the LCM at the OPAC that has faults, type:
>DISP STATE ISTB LCM
and press the Enter key.
4
To post the LCM at the OPAC with the alarm condition, type:
>POST LCM site frame lcm
and press the Enter key.
where
site
is the site name of the OPAC (alphanumeric)
frame
is the frame number of the OPAC (0 to 511)
lcm
is the number of the LCM
5
To determine the fault indicators, type:
>QUERYPM FLT
and press the Enter key.
If fault
is ringing generator
is CBsy (C-side busy)
is SysB
is ManB
DMS-100 Family OPAC Maintenance Manual XPM12 and up
Alarm clearing procedures 7-43
major
(continued)
Do
step 6
step 9
step 16
step 17
RLCM

Advertisement

Table of Contents
loading