Opac Critical - Nortel DMS-100 Series Maintenance Manual

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

7-2
7-2
Alarm clearing procedures
OPAC
critical
Alarm display
CM
.
Application
Use this procedure to recover service in an OPAC when both units of the
line concentrating module (LCM) are out of service. This condition always
produces a central side busy (CBsy) alarm.
In the MAP display, the OPAC alarm appears under the PM header of the
alarm banner. The message indicates a critical alarm condition in the OPAC.
The n indicates the number of OPACs with alarms. The *C* that appears
under the message indicates the alarm is critical.
Action
This procedure contains a summary flowchart and a list of steps. Use the
flowchart to review the procedure. Follow the steps to perform the
procedure.
Note: The numbers displayed in the flowchart do not match the step-action
numbers. The numbers indicate movement in the flowchart.
297-8211-550 Standard 05.01 August 1999
7-2
MS
IOD
Net
.
.
.
PM
CCS
Lns
nLCM
.
.
*C*
Trks
Ext
Appl
.
.
.