7-56 Alarm clearing procedures
OPAC (RG)
major
(continued)
9
10
297-8211-550 Standard 05.01 August 1999
To test the ManB LCM, type:
>TST UNIT unit_no
or
>TST PM
and press the Enter key.
where
unit_no
is the number of the ManB LCM unit.
Example of a MAP response :
LCM REM1
14
LCM REM1
RLCM
Initiated
LCM REM1
14
LCM
REM1
LCM
REM1
Tst Failed: (Reason for failure)
LCM
REM1
LCM
REM1
If TST
passes
fails
After you replace the ringing generator (NT6X60), test the LCM in the OPAC
again. To test the LCM, type:
>TST PM
and press the Enter key.
If TST
passes
fails
1
Unit 1
InSvce Test Initiated
RSC0 14
1
Unit 1
Unit 1 Tst Failed: (Reason for failure)
1
or
14
1
Unit 1
InSvce Test Initiated
14
1
Unit 1
Tst passed14
or
14
1
Unit 1
InSvce Test Initiated
14
1
Unit 1
Tst passed
Do
step 11
step 14 (replace the ringing
generator)
Do
step 11
step 16
InSvce Test
1
Unit 1