Electrical System - Nortel DMS-100 Series Maintenance Manual

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

2-14 OPAC maintenance overview

Electrical system

The electrical system consists of several components. These components
include the ac interface and distribution, ac generator transfer switch, the
modular supervisory panel (MSP), the rectifiers and battery control unit
(BCU). Additional components include the batteries and associated cabling
and ground bars.
The following sections describe the powering system and electrical
equipment in greater detail.
Power requirements
The OPAC supports a maximum of three 25 A rectifier modules. These
modules power several different equipment and system configurations. A
list of the business supply features appears in the following table.
Commercial power features
Power
features
Source
Surge
Arrestor
Outlets
Rectifiers
Battery
backup
Emergency
connector
Emergency
transfer
An OPAC with 640 lines requires two 25 A, 52.5 V rectifier modules and
200 Ah battery reserve to maintain stand-by power.
297-8211-550 Standard 05.01 August 1999
Requirements
Single phase, 3-wire commercial power, 176–264 V, 47–63 Hz
ac small amount at 100 A
Metal oxide, varistor solid state, Joslyn Number 1250–33
One dedicated outlet for ac heaters and two 120 V ac support
outlets with a standard GFC Interrupt.
A maximum of three NT MPR25 (NT5C06) 25 A rectifier
modules.
A maximum of 300 Ah provide 6.6 h minimum reserves under
maximum power drain.
A 60 A Hubbel emergency generator connector.
An attached power pedestal with a double-pole, double-throw
(DPDT) knife switch.
Perform an emergency transfer with the transfer switch and
generator connector, Hubbell Part Number 460B12W.

Advertisement

Table of Contents