Nortel DMS-100 Series Maintenance Manual page 315

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

Clearing an RMM major alarm
At the MAP terminal
1
To silence the alarm, type
>MAPCI;MTC;PM;SIL
and press the Enter key.
2
To identify the RMM that has faults, type
>DISP STATE SYSB RMM
and press the Enter key.
Example of a MAP response:
SysB
RMM: 2
3
To post the SysB RMM identified in step 2, type
>POST RMM rmm_no
and press the Enter key.
where
rmm_no
is the number of the RMM that has faults
4
To manually busy the RMM posted in step 3, type
>BSY
and press the Enter key.
5
To perform a test on the RMM that has faults, type
>TST
and press the Enter key.
If test
passes
fails because of load failure
fails because of C-side links
unavailable
fails and the system generates a
card list
DMS-100 Family OPAC Maintenance Manual XPM12 and up
Alarm clearing procedures 7-79
major
Do
step 32
step 6
step 24
step 33
RMM
(continued)