Nortel DMS-100 Series Maintenance Manual page 246

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

7-10 Alarm clearing procedures
OPAC
critical
(continued)
18
19
20
21
297-8211-550 Standard 05.01 August 1999
Determine if the OPAC has the ESA timer set for manual recovery from ESA.
To access table OFCENG, type
>TABLE OFCENG
and press the Enter key.
To check the OPAC exit time, type
>POS RLCM_XPMESAEXIT
and press the Enter key.
Example of a MAP response:
PARMNAME
–––––––––––––––
RLCM_XPMESAEXIT
If PARMVAL
is set to zero
is greater than
zero
Before manually restoring the OPAC from ESA, check to see if links to the
OPAC are stable. To find the link numbers for this OPAC, type
>TRNSL C
and press the Enter key.
Example of a MAP response:
Link
0:
LTC 1
Link
1:
LTC 1
Link
2:
LTC 1
Link
3:
LTC 1
where
the number that appears next to the word "Cap" is the host XPM link number.
To access the CARRIER level of the MAP terminal, type
>TRKS;CARRIER
and press the Enter key.
PARMVAL
0
Do
step 20
Allow the system to recover the OPAC. Go to step 27.
0;Cap MS;Status:OK
2;Cap MS;Status:OK
3;Cap
S;Status:OK
4;Cap
S;Status:OK
;MsgCon:OPN
;MsgCon:OPN