Nortel DMS-100 Series Maintenance Manual page 425

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

5
Go to the peripheral module (PM) level of the MAP display and post the RMM
by typing
>PM;POST RMM rmm_no
and pressing the Enter key.
where
rmm_no
is the number of the RMM shelf where the card is to be replaced
Example of a MAP response:
SysB
PM
0
RMM
0
RMM
0
At the RMM
6
WARNING
Static electricity damage
Wear a wrist strap connected to the wrist strap
grounding point at the top of each equipment rack,
(Bay 0, 1, 2, and 3), while handling circuit cards. This
protects the cards against damage caused by static
electricity.
Busy the RMM by typing
>BSY
and pressing the Enter key.
7
Replace the NT3X09 card using the procedure "Replacing a card." When you
have completed the procedure, return here.
DMS-100 Family OPAC Maintenance Manual XPM12 and up
ManB
Offl
2
2
0
0
InSv
Card replacement procedures 8-59
RMM
CBsy
ISTb
0
7
0
0
NT3X09
(continued)
InSv
21
6