Nortel DMS-100 Series Maintenance Manual page 660

Outside plant access cabinet (opac)
Hide thumbs Also See for DMS-100 Series:
Table of Contents

Advertisement

13-12 Routine maintenance procedures
Battery inspection and cleaning
OPAC
(continued)
Battery inspection and cleaning
At the OPAC site
1
At the MAP terminal
2
3
4
297-8211-550 Standard 05.01 August 1999
DANGER
Hazardous chemicals
Battery chemicals can be dangerous and potentially
explosive. Use caution.
Inspect battery packs, connectors, floor, and shelves for moisture or corrosion.
If moisture or corrosion
is present
is not present
To access the OPMPES MAP display, type
>MAPCI;MTC;PM;PES
and press the Enter key.
To post the appropriate alarm state, type
>POST alarm_state
and press the Enter key.
where
alarm_state
is RED, AMBER, GREEN, or OFFL
Note: This command posts the alarm state and all the PMs in the alarm state,
and displays the first PM in the set. Use the NEXT command to scroll through
the posted PMs until the MAP terminal displays the appropriate OPAC.
To disable the automatic battery rotation and testing, type
>AUDIT DISABLE
and press the Enter key.
Do
step 2
step 14