Cable/Terminal Specifications

Installation should conform to the NEC Article 110 ("Requirements for Electrical Installations"), all
regulations of the Occupational Safety and Health Administration, and any other applicable national,
regional, or industry codes and standards.
Cable sizes for each typeform are listed in the standard drawings that accompany the received system.
Note:
The following ratings are guidelines and shall not be the sole determining factor of the
lug or wire size used with the WX9 ASD. Application-specific applicables, wire
insulation type, conductor material, and local and regional regulations are but a few of
the considerations when selecting the actual lug and wire type to be used with the WX9
ASD.
Note:
Cable/Terminal specifications are based on the rated current of the WX9 ASD and
do not include the 10% Service Factor.
Note:
Use only 75° C copper wire/cable for motor and power connections.
For more installation information, see the section titled
accompanying drawings for specifics on the actual system being connected.
Model
Number
WX94
Note:
For Lug Size values, the non-parenthesized number indicates the quantity of cables to
be used for the parenthesized recommended size range [i.e.,
sizes 1/0 to 750 MCM].
WX9 ASD Installation and Operation Manual
Table 20. 460-Volt WX9 ASD Cable/Terminal Specifications.
Cable Size
AWG
AM, FM, II
Terminals
50K
60K
#20
(3-Core Shield)
70K
80K
Installation and Connections on pg. 14
Lug Size Range
AWG or MCM/kcmil
Input/Output Power
TB1 Terminal
Strip
3Ø-Input
#18
4 (3/0 -
(2-Core Shield)
500MCM)
3Ø-Output
4 (1/0 -
750MCM)
4 (1/0 - 750) = Four cables of
and the
203