F826
ASD to ASD Communication (RS232/RS485)
Program Communications Communication Settings
In a master/follower configuration, this setting determines the output parameter
of the master ASD that will be used to control the applicable follower ASDs.
Note:
Select No Follower if
controller. Otherwise, an EOI failure will result.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Settings:
0 — Normal (no follower)
1 — Frequency Command
2 — Output Command Frequency
3 — Torque Command
4 — Output Torque Command
Command Request Disposition on Error
Program Communications Scan Settings
In the event of a communication error during a transmission, the command that
was transmitted may be cleared or held.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Settings:
0 — Command Request Cleared
1 — Command Request Held
Input Reference 1
Program Communications Scan Settings
Not used.
Input Reference 2
Program Communications Scan Settings
Not used.
Input Reference 3
Program Communications Scan Settings
Not used.
Input Reference 4
Program Communications Scan Settings
Not used.
Input Reference 5
Program Communications Scan Settings
Not used.
176
F806
is configured as a Master Output
Direct Access Number — F826
Parameter Type — Selection List
Factory Default — Normal (no follower)
Changeable During Run — Yes
Direct Access Number — F830
Parameter Type — Selection List
Factory Default — Command Request
Cleared
Changeable During Run — Yes
Direct Access Number — F831
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — Yes
Direct Access Number — F832
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — Yes
Direct Access Number — F833
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — Yes
Direct Access Number — F834
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — Yes
Direct Access Number — F835
Parameter Type — Selection List
Factory Default — 0
Changeable During Run — Yes
WX9 ASD Installation and Operation Manual
F835