Toshiba WX9 ASD Installation & Operation Manual page 122

Table of Contents

Advertisement

F228
BIN Reference Point 1
Program Torque Setpoints
Program Frequency Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control or the Torque Control mode.
The discrete input terminals of the Terminal Board are used as the BIN
terminals.
BIN Speed Control Setup
Perform the following setup to allow the system to receive Speed control input
at the BIN terminals:
Program Fundamental Standard Mode Selection Frequency
Mode 1 Binary/BCD.
Program Fundamental Standard Mode Selection Command
Mode Selection Terminal Board.
Program Terminal Input Terminals; select and set the desired
discrete input terminals to Binary Bit(s) 
0 – 7 (or 0 – MSB). The binary terminal input byte will control the
speed of the motor.
Program Terminal Input Terminals; select and set a
discrete input terminal to Binary Data Write. Activation of the
Binary Data Write terminal will transfer the status of the Binary
Bit(s) 0-7 (or 0-MSB) to the control board for speed control.
Set BIN Point 1 Frequency (F229).
Set the BIN value (% of 255
Point 1.
Note: 255
is the decimal equivalent of the 8-bit BIN word with
D
all input terminals set to one (255 decimal = 11111111
binary).
Set BIN Point 2 Frequency (F231)
Set the BIN value (% of 255
Point 2.
Provide a Run command (F and/or R).
Once set, as the BIN signal changes are transferred to the control board, the
directional information, the output frequency, or the output torque of the drive
will vary in accordance with the above settings.
This parameter sets BIN Reference Point 1 (direction/torque/frequency) and is
entered as 0 to 100% of the BIN binary input byte 11111111 (255
binary bit(s) 0 - MSB.
BIN Point 1 Frequency
Program Frequency Speed Reference Setpoints
This parameter is used to set the direction, gain, and bias of the BIN binary input
terminals when these terminals are used as the control input while operating in
the Speed Control mode.
This parameter sets BIN Point 1 Frequency and is the frequency that is
associated with the setting of F228.
See BIN Reference Point 1
110
) (F228) that represents BIN Reference
D
) (F230) that represents BIN Reference
D
)
(F228
for additional information on this setting.
Direct Access Number — F228
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.00
Units — %
Frequency Settings
Torque Settings
) or the
D
Direct Access Number — F229
Parameter Type — Numerical
Factory Default — 0.0
Changeable During Run — Yes
Minimum — - (Maximum Freq. (F011))
Maximum — + (Maximum Freq. (F011))
Units — Hz
WX9 ASD Installation and Operation Manual
F229

Advertisement

Table of Contents