F802
ASD Number
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
assigning an identification (ID) number to each ASD in the communications
network.
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the parameter settings of the ASD.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Communications Time-Out RS232/RS485
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
setting the time that no activity may exist over the communications link before
the link is severed (Time-Out).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the settings of the ASD.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Communications Time-Out Action (RS232/RS485 and TTL)
Program Communications Communication Settings
This parameter plays a role in the setup of the communications network by
determining the action to be taken in the event of a time-out (Time-Out Action).
The communications network includes other ASDs and Host/Control computers
that monitor the status of the ASD(s), transfers commands, and loads or
modifies the settings of the drive.
Note:
Changes made to this parameter require that the power be cycled
(off then on) for the changes to take effect.
Settings:
Setting
RS232/RS485
0
No action
1
2
3
No action
4
5
6
No action
7
8
172
nTTL
No action
Alarm
No action
Trip
No action
Alarm
Alarm
Alarm
Trip
Alarm
Trip
Alarm
Trip
Trip
Trip
Direct Access Number — F802
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 255
Direct Access Number — F803
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — Seconds
Direct Access Number — F804
Parameter Type — Selection List
Factory Default — Trip
Changeable During Run — Yes
WX9 ASD Installation and Operation Manual
F804