Toshiba WX9 ASD Installation & Operation Manual page 156

Table of Contents

Advertisement

F440
Power Running Torque Limit 1
Program Torque Torque Limit Settings
This parameter determines the source of the control signal for the positive
torque limit setting. If Setting is selected, the value set at
Power Running Torque Limit 1 input.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F441)
Power Running Torque Limit 1 Level (250% = disabled)
Program Torque Manual Torque Limit Settings
This parameter provides a value for the Power Running Torque Limit 1
setting if Setting is selected at F440. This value provides the positive torque
upper-limit for the 1 motor.
Regenerative Braking Torque Limit 1
Program Torque Torque Limit Settings
This parameter determines the source of the Regenerative Torque Limit
control signal. If Setting is selected, the value set at
parameter.
Settings:
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F443)
Regenerative Braking Torque Limit 1 Level
(250% = disabled)
Program Torque Manual Torque Limit Settings
This parameter provides a value to be used as the Regeneration Torque
Limit 1 if Setting (F443) is selected at F442.
Power Running Torque Limit 2 Level (250% = disabled)
Program Torque Manual Torque Limit Settings
This parameter is used to set the positive torque upper-limit for the 2 Motor
Profile when multiple motors are controlled by a single drive or when a single
motor is controlled by multiple profiles.
144
F441
is used as the
F443
is used for this
Direct Access Number — F440
Parameter Type — Selection List
Factory Default — Setting (F441)
Changeable During Run — Yes
Direct Access Number — F441
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F442
Parameter Type — Selection List
Factory Default — Setting (F443)
Changeable During Run — Yes
Direct Access Number — F443
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F444
Parameter Type — Numerical
Factory Default — 250.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
WX9 ASD Installation and Operation Manual
F444

Advertisement

Table of Contents
loading

Table of Contents