F661
Multiplying Input Selection
Program Feedback Override Control
This parameter Enables/Disables the feature that allows for the external
adjustment of the Output Frequency.
Selecting either of the input methods listed enables this feature. The selected
input is used as a multiplier of the programmed Output Frequency.
If operating using the CN8 Option and Setting (F729) is selected, the value
entered at CN8 Option Override Multiplication Gain
multiplier of the commanded frequency.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F729)
AM Output Terminal Function
Program Terminal Analog Output Terminals
This setting determines the output function of the AM analog output terminal.
The AM output terminal produces an output voltage or current that is
proportional to the magnitude of the function assigned to this terminal. The
available assignments for this output terminal are listed in
To read Voltage at this terminal, connect a 100 – 500 resistor from AM (+) to
AM (-). The voltage is read across the 100 – 500 resistor.
To read Current at this terminal, connect a 100 – 500 resistor in series from
AM (+), through the current meter, to AM (-).
The AM Terminal Adjustment (F671) is used to calibrate the output signal for
a proper response. SW-2 at the Terminal Board may be switched to allow for
the full-range output to be either 0 – 1 mA or 4 – 20 mA when providing an
output current, or either 0 – 1 or 1 to 7.5 volts when providing an output voltage
at this terminal.
166
Direct Access Number — F661
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
(F729)
is used as the
Direct Access Number — F670
Parameter Type — Selection List
Factory Default — Output Current
Changeable During Run — Yes
Table 9 on pg.
181.
WX9 ASD Installation and Operation Manual
F670