Toshiba WX9 ASD Installation & Operation Manual page 154

Table of Contents

Advertisement

F425
Forward Speed Limit Input Selection
Program Torque Torque Control
This parameter Enables/Disables the Forward Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the
forward speed limit is controlled by the terminal selected here. If Setting is
selected, the value set at
F426
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F426)
Forward Speed Limit Input Level
Program Torque Torque Control
This parameter provides a value to be used as the Forward Speed Limit setting
if Setting is selected at F425.
Reverse Speed Limit Input Selection
Program Torque Torque Control
This parameter Enables/Disables the Reverse Speed Limit Input control
function. When enabled and operating in the Torque Control mode, the reverse
speed limit is controlled by the terminal selected here. If Setting is selected, the
value set at
F428
is used as the Reverse Speed Limit input.
Settings:
0 — Disabled
1 — VI/II
2 — RR
3 — RX
4 — RX2
5 — Setting (F428)
Reverse Speed Limit Input Level
Program Torque  Torque Control
This parameter provides a value to be used as the Reverse Speed Limit setting
if Setting is selected at F427.
142
is used as the Forward Speed Limit input.
Direct Access Number — F425
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F426
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (F012)
Units — Hz
Direct Access Number — F427
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F428
Parameter Type — Numerical
Factory Default — 60.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — Upper-Limit Freq. (F012)
Units — Hz