F615
Over-Torque Trip Selection
Program Protection Over-Torque Parameters
This parameter Enables/Disables the Over-Torque Tripping function.
When enabled, the ASD trips if an output torque value greater than the setting
of
F616
or
F617
exists for a time longer than the setting of F618.
When disabled, the ASD does not trip due to over-torque conditions.
Note:
A discrete output terminal may be activated when an over-torque
alarm occurs if so configured (see F130).
Settings:
0 — Disabled
1 — Enabled
Over-Torque Detection Level During Power Running
Program Protection Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping. This setting is a percentage of the maximum rated torque of the
drive.
This function is enabled at Over-Torque Trip Selection (F615).
Over-Torque Detection Level During Regenerative Braking
Program Protection Over-Torque Parameters
This parameter sets the torque threshold level that is used as a setpoint for over-
torque tripping during regeneration. This setting is a percentage of the
maximum rated torque of the drive.
This function is enabled at Over-Torque Trip Selection (F615).
Over-Torque Detection Time
Program Protection Over-Torque Parameters
This parameter sets the amount of time that the over-torque condition may
exceed the tripping threshold level set at
This function is enabled at F615.
Cooling Fan Control
Program Protection Special Protection Parameters
This parameter sets the cooling fan run-time command.
Settings:
0 — Automatic
1 — Always On
160
and
F616
F617
before a trip occurs.
Direct Access Number — F615
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — Yes
Direct Access Number — F616
Parameter Type — Numerical
Factory Default — 150.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F617
Parameter Type — Numerical
Factory Default — 150.0
Changeable During Run — Yes
Minimum — 0.00
Maximum — 250.0
Units — %
Direct Access Number — F618
Parameter Type — Numerical
Factory Default — 0.50
Changeable During Run — Yes
Minimum — 0.00
Maximum — 100.0
Units — Seconds
Direct Access Number — F620
Parameter Type — Selection List
Factory Default — Automatic
Changeable During Run — Yes
WX9 ASD Installation and Operation Manual
F620